title.gif (15257 bytes)

XAHC FEATURES


UNIT STANDARD FEATURES INCLUDE:

-FULL 1" FIBERGLASS INSULATION ON ALL EXTERNAL SURFACES FOR SUPERIOR NOISE REDUCTION
-QUALITY PUMP WITH BRASS/BRONZE CASTING AND NON-METALLIC IMPELLER FOR LONG LIFE
-HORIZONTAL AND VERTICAL (UPFLOW OR DOWNFLOW) INSTALLATION
-EXCLUSIVE BACKWARD INCLINED EXTERNAL ROTOR BLOWER FOR LOW NOISE AND POWER USE
-ALL COPPER PIPING WITH BRASS/BRONZE FIXTURES FOR DEPENDABLE LONGER LIFE
4 WIRE LOW VOLTAGE (24VAC) CONTROL AND RELAYS BUILT -IN (ALLOWS"FAN ONLY MODE")
- PREPAINTED GALVANIZED STEEL WITH EXTREMELY DURABLE FINISH
-CSA ELECTRICAL INSPECTION

UNIT TECHNICAL INFORMATION

POWER

FAN

PUMP

MIN.

MAX.

RETURN

MODEL

INPUT

FLA

FLA

CIRCUIT

FUSE

DUCT SIZE

(VAC)

(AMPS)

(AMPS)

(AMPS)

(AMPS)

(INCHES)

XAHC-12

120

.85

0.74

2.0

15

12 X 6

XAHC-18

120

.85

0.74

2.0

15 18 X 8

XAHC-32

120

1.7

0.74 3.0 15 24 X 10

HEATING CAPACITY (BTU/HR)

  

 

 

ENTERING AIR TEMP.@ 65 DEG F

 

  ENTERING AIR TEMP.@ 70 DEG F     

FLOW

EWT EWT EWT EWT EWT EWT EWT EWT

MODEL

RATE

130 140 160 180 130 140 160 180
GPM DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F
XAHC-12 3 11,000 12,500 16,500 20,000 10,000 12,000 15,500 19,000
XAHC-18 3 16,500 19,000 24,500 30,000 15,000 18,000 23,000 28,500
XAHC-32 3 30,000 34,500 44,000 54,000 27,500 32,000 42,000 51,500

BLOWER CAPACITY AT SELECTED EXTERNAL STATIC PRESSURES

UNIT CFM BLOWER ON FACTORY SETTINGS

MODEL

0.05"

0.10" 0.20" 0.30" 0.40" 0.50"
XAHC-12 340 330 310 290 270 250
XAHC-18 365 350 330 310 290 270
XAHC-32 665 655 640 625 605 580

XAHC MEASUREMENTS