AHC FEATURES


UNIT STANDARD FEATURES INCLUDE:

-FULL 1" FIBERGLASS INSULATION ON ALL EXTERNAL SURFACES FOR SUPERIOR NOISE REDUCTION
-FACTORY INSTALLED HEATING AND AIR CONDITIONING COILS
-QUALITY PUMP WITH BRASS/BRONZE CASTING AND NON-METALLIC IMPELLER FOR LONG LIFE
-HORIZONTAL INSTALLATION ONLY
-EXCLUSIVE BACKWARD INCLINED EXTERNAL ROTOR BLOWER FOR LOW NOISE AND POWER USE
-ALL COPPER PIPING WITH BRASS/BRONZE FIXTURES FOR DEPENDABLE LONGER LIFE
4 WIRE LOW VOLTAGE (24 VAC) CONTROL AND RELAYS BUILT-IN
- PREPAINTED GALVANIZED STEEL WITH EXTREMELY DURABLE FINISH
-CSA ELECTRICAL INSPECTION

UNIT TECHNICAL INFORMATION

POWER

FAN

PUMP

MIN.

MAX.

RETURN

MODEL

INPUT

FLA

FLA

CIRCUIT

FUSE

DUCT SIZE

(VAC)

(AMPS)

(AMPS)

(AMPS)

(AMPS)

(INCHES)

AHC20-12

120

.85

0.74

2.0

15

18 X 8

AHC31-18

120

1.7

0.74

3.0

15 24 X 10

HEATING CAPACITY (BTU/HR)

  

 

 

ENTERING AIR TEMP.@ 65 DEG F

 

  ENTERING AIR TEMP.@ 70 DEG F     

FLOW

EWT EWT EWT EWT EWT EWT EWT EWT

MODEL

RATE

130 140 160 180 130 140 160 180
GPM DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F
AHC20-12 3 18,500 21,500 27,500 33,000 17,000 20,000 26,000 32,000
AHC31-18 3 28,500 33,000 42,500 51,500 26,500 31,000 40,000 49,500

COOLING CAPACITY (BTU/HR)

MODEL COOLING CONDITIONS
AHC20-12 12,000 BTU @45 F EVAP. TEMP. WITH R22@ 360 CFM
AHC31-18 18,000 BTU @45 F EVAP. TEMP. WITH R22@ 585 CFM

BLOWER CAPACITY AT SELECTED EXTERNAL STATIC PRESSURES

UNIT CFM BLOWER ON FACTORY SETTINGS

MODEL

0.05"

0.10" 0.20" 0.30" 0.40" 0.50"
AHC20-12 410 400 375 360 340 315
AHC31-18/ 625 620 600 585 560 530

AHC MEASUREMENTS